Electrical technical data
Power supply
9 ÷32 Vdc (polarity protected)
Electronic board input
for digital sensors with I2CBus interface
Power supplied to sensor 3.3Vdc max 5mA
Accuracy (*)
(*) @25°C
refer to the specific graphs
Temp: ± 0.3°C @ -40÷ 90°C
RH: 2% @ 0÷100°%
refer to the technical data of the sensor installed
Resolution
Temperature: 0.1°C
Relative Humidity: 0.1%
Current consumption
<4mA with RS485 (<10mA at power on for approx. 8mS)
Communication protocol
Modbus RTU (max. baud rate 38.400)
Serial interface
RS-485 (not insulated)
Maximum connection distance
1000 meters, this distance depends on the power supply voltage and the type of cable used to connect the various devices
Maximum devices on network
Maximum 256 nodes (it is recommended to use isolators / repeaters along the serial line)
Input/Output insulation
None
Indicator LED
Blue LED, power supply and device operations indicator
Red LED (ERR), sensor error indicator
White LEDs (TX and RX), serial transmission and reception indicators
Electronic board operating temperature
-40 ÷80°C
EMC
In accordance to BS EN 61326-1:2013 (UKCA)
In accordance to EN 61326-1:2013 (CE)
Configuration
By using the EVOPLATFORMSET configuration kit (a PC with Windows OS is required).
International protection marking (*)
(*) According to IEC 60529
IP65/67
Compatible sensors
Temperature / Humidity sensor (cod. EVO033)
Ambient light sensor (cod. EVO035)
Main device design parameters
Varaibles measured by the sensors
Minimum and maximum peak of measured variables
Offset for correction of the measured variables
Serial communication and power-on watch-dog
Option
“T” distributor Female / Male / Female M12 x 5 poles
Extension cables with M12 overmoulded female and male connectors
Wall mounting bracket
EVOPLATFORMSET configuration kit
Note
for each sensor it is necessary to download the communication driver on the EvominiSER. The device is supplied with the communication driver for the temperature / humidity sensor